ANAFAZE SYSTEM 32 connections for a single unit are as follows:

Black Box
COMPUTER LD485A SYSTEM 32

+485 Output (Start bit +5v) TXA RX+ #3

-485 Output (Start bit 0v) TXB RX- #4

+485 Input RXA TX+ #1

-485 Input RXB TX- #2

Shield-------Earth Ground---------Shield Do not Ground

Note: Connect the shields to earth ground only at the computer or other 485
interface. No shield connection is required at the SYSTEM 32. Connect a 200
ohm terminating resistor between RX- and RX+ at the SYSTEM 32.

For multiple units connect the system as follows:

Black Box SYSTEM 32 SYSTEM 32
LD485A [1] [n]

TXA RX+ #3 RX+ #3 ---|
200 ohms
TXB RX- #4 RX- #4 ---|

Ground

RXB TX+ #1 TX+ #1

RXA TX- #2 TX- #2

Ground