8

2.5 CONTROL AND ALARM OUTPUTS
32 Individually selectable control outputs:

Digital Outputs:

Time proportioning, On/Off, Alarms: voltage
output: 5VDC at 6ma maximum for solid state or
other relays.

Analog:

voltage or current: selectable (4 to 20ma, or 0 to 5
volts).

2.6 DIGITAL INPUT OR OUTPUT
24 DigitalOutputs:

TTL Level: true= < 0.4v @ 6ma false = > 3.9v
@ 6ma

16 Digital Inputs:

TTL Level:

2.7 ANALOG OUTPUTS
Types:

0 to 5Vdc at 5ma max.
4-20ma at 8Vdc max [maximum loop impedance
400 ohms].

Both are available at the output terminals of each
output. Either can be used -- no jumpers are
required. DO NOT USE BOTH ON SAME
OUTPUT.

Accuracy:

+3%

Resolution:

0.4%

2.8 GENERAL
Power input:

120VAC, 60Hz, to power supply.
modules require 5vdc @ 5A max [6 slot].

Operating ambient:

0 to 50 C.

Humidity:

10% to 90%, non-condensing.

Enclosures:

NEMA 4, 12, 13 and others optional.

Physical:

6 Slot Housing: 16.7" wide [19" standard rack
mount], 12.5" high, 7.5" deep.
3 Slot Housing: 10.7" wide.

Mounting:

4 mounting holes for standard rack or panel
mounting -- see outline drawings.

Weight:

maximum 20 pounds depends on plug modules
selected.