Troubleshooting — spark-pilot boilers

11c

The information on this page and
pages 53 through 59 apply only to
spark-ignited pilot CGa boilers.
These boilers are equipped with an
ignition control module that has in-
dicator lights to show control status.
Charts

2

through

7

, pages 54-59,

help you identify problems based
on indicator light conditions.

Figure 29 CGa Ignition control module

Control module

Solder or water

splatter between plugs and circuit board

can cause improper operation of control module. Place a

shield over the boiler internal controls and components

during installation. Failure to comply could result in

severe personal injury, death or substantial property

damage.

Make sure

ground wiring

is installed per wiring

diagram. Good grounding is extremely important for

proper operation.

Control indicator lights —
LOCKOUT modes

See

Charts 1

through

7

in this section for detailed troubleshooting procedures.

To reset control after a lockout, turn off power at the 10 VAC service switch or turn
down all thermostats. Wait 45 seconds. Then restore power or call for heat.

POWER light flashing alone

Usually indicates reversed polarity of 10 VAC power wires.

POWER and TSTAT CIRC lights flashing

Usually indicates stray voltage on external thermostat circuit wires (usually due to
miswired 3-wire zone valve).

POWER and DAMPER lights flashing

Usually indicates damper circuit is closed when it should not be, or damper failed
to close within 5 minutes.

POWER and FLAME lights flashing

Usually indicates false flame sense or flame sensed when it shouldn’t be there.

Control indicator lights —
NON-LOCKOUT modes

POWER light on and FLAME light flashing

Usually indicates pilot flame was not established within 15 seconds from application
of spark. Control will flash light, but will continue to cycle indefinitely until flame
is established or problem is corrected.

POWER light on and DAMPER light flashing

Usually indicates the damper circuit opened during the run cycle.

Troubleshooting the control module

See

Figure 30

, page 53, for location of harness plug receptacles and plugs on the

control module.