Troubleshooting — spark-pilot boilers, Gold cga gas-fired water boiler — boiler manual – Weil-McLain Gold CGa User Manual

Page 58

Advertising
background image

GOLD CGa Gas-Fired Water Boiler — Boiler Manual

58

Part Number 550-101-009/0107

TURN OFF POWER to

boiler at service switch or

breaker.

• Remove base access panel (see

Figure 32, item 4, page 62 for

location).

• Verify inlet gas pressure at gas

valve:
Natural gas — 5.0" w.c. min/14.0"

w.c. max
Propane — 11.0" w.c. min/14.0"

w.c. max

Is gas present at gas valve inlet and

within above range?

Electrical shock hazard — Wherever you see

TURN OFF POWER , follow the instructions. Failure to follow

instructions could result in severe personal injury, death or substantial property damage.

No

Yes

• Is pilot flame visible through inspection port?

• Are main manual shutoff valve and boiler gas valve open?

No

Yes

• s

TURN OFF POWERs to boiler at service switch or breaker.

• Open main manual shutoff valve and boiler gas valve (per

Operating instructions in this manual). Wait at least 45

seconds.

• Turn on power at service switch or breaker. Allow boiler to cycle.

Does

FLAME light flash now?

No

Yes

• Boiler should be in

normal operating

sequence.

• Observe operation

until thermostat is

satisfied and blower

has completed its

post-purge cycle.

• Make sure ground wire

terminal is securely fastened

to control module mounting

screw.

• Check the voltage across

main gas valve terminals of

the gas valve.

Is 24 VAC present there?

No

Yes

• Check the voltage across

main gas valve terminals of

the gas valve.

Is 24 VAC present there?

No

Yes

No

Yes

• Contact gas supplier to correct

pressure or gas supply.

• If the wiring from the

control module to gas

valve is intact, replace the

control module.

• Retest.

TURN OFF POWER to boiler at service switch or breaker.

• Check flame signal — Detach sense lead from igntion control

(Figure 30, item 8, page 53).

• Connect

negative lead of MICROAMMETER to control sense

terminal (Figure 30, item 8, page 53). Connect positive lead of

MICROAMMETER to sense wire.

• DISCONNECT

red wire connected to man gas valve terminal of

the gas valve.

• Turn on power to boiler and allow to cycle. As soon as pilot is

burning, the MICROAMMETER should read at least 1.0

microamp.

Is flame signal at least 1.0 microamp?

No

Yes

• If the wiring from the

control module to gas

valve is intact, replace the

control module and retest.

• Verify inlet gas pressure at gas valve:

Natural gas — 5.0" w.c. min/14.0" w.c. max
Propane — 11.0" w.c. min/14.0" w.c. max

Is gas present at gas valve inlet and within above range?

No

Yes

TURN OFF POWER to

boiler at service switch or

breaker.

• Remove base access panel

(see

Figure 32, item 4,

page 62 for location).

• Verify pilot gas line is not

kinked, obstructed or damaged

and is correctly attached to

pilot and gas valve.

• Verify pilot ignition electrode,

electrode ceramic and spark

lead wire from control are in

good condition. Spark gap

should be approximately 1/8".

• Correct any above problems,

replacing pilot if burner or

wiring is damaged.

• Reinstall base access panel to

operate boiler for retest after

any changes or corrections.

• If none of the above corrects

problem, then replace the

control module, reinstall base

access panel, and retest.

• Verify pilot burner is securely

attached to pilot bracket, bracket

is securely attached to cross tie,

and there is no corrosion on the

parts which would affect the

ground path for flame sense.

• Verify that pilot flame rod, flame

rod ceramic and lead wire from

control module to flame rod are in

good condition.

• Correct any above problems,

replacing pilot if burner or wiring

is damaged.

• If none of the previous steps

(including replacing pilot)

corrects problem, then replace

the control module, reinstall

base access panel and retest.

CHART 6 — Spark-ignited pilot FLAME light flashing and POWER light on steady

ALSO — Troubleshooting failure to establish main flame

11c

Troubleshooting — spark-pilot boilers

(continued)