Start-up — if boiler doesn’t start . . .
7c
1. Loose connections, blown fuse or service switch
off?
2. High limit switch set below boiler water tempera-
ture?
3. Thermostat set below room temperature?
4. Gas not turned on at meter or boiler?
5. Incoming gas pressure less than:
5” w.c. for natural gas?
11” w.c. for propane gas?
6. If none of the above corrects the problem, refer to
Troubleshooting
, Section
11
of this manual.
Check for: