Start-up — if boiler doesn’t start – Weil-McLain GOLD CGS-4E User Manual

Page 30

Advertising
background image

Part number 550-110-282/1108

30

GOLD

CGs-4E Gas-Fired Water Boiler — Boiler Manual

Start-up — if boiler doesn’t start . . .

7c

1. Loose connections, blown fuse or service switch

off?

2. High limit switch set below boiler water tempera-

ture?

3. Thermostat set below room temperature?

4. Gas not turned on at meter or boiler?

5. Incoming gas pressure less than:

5” w.c. for natural gas?

11” w.c. for propane gas?

6. If none of the above corrects the problem, refer to

Troubleshooting

, Section

11

of this manual.

Check for: