CGs-4E Gas-Fired Water Boiler — Boiler Manual

Operation — sequence

9a

1.

Read appropriate Operating instructions

in Section

9c

.

This information is also located on a label on the inside of

the boiler jacket door panel.

2.

Raise

room thermostat to call for heat.

3.

Circulator energizes.

If limit circuit is closed, the inducer

starts. After pressure switch proves proper airflow, control

module initiates a 30-second prepurge.

4.

Control module sparks

the pilot and opens pilot valve in

main gas valve.
a. If pilot

does not

light within 15 seconds, pilot valve is

closed and spark generator is turned off. Control mod-

ule initiates a 15-second postpurge, then starts a new

cycle.

b. If pilot

does

light and control module senses flame

current, spark generator is turned off and main valve

opens.

5. The CGs-4E timer relay delays high fire for the first 60 seconds

of main flame.

6. During

main burner operation

:

a. Control module monitors pilot flame current.

If signal

is lost

, main valve closes, spark generator activates and

sequence returns to step

4

.

b.

If power is interrupted

, control system

shuts off

pilot

and main gas valves and restarts at step

1

when power is

restored.

7. In the event the

limit control shuts down the boiler

— The

control module closes the pilot and main gas valves, but keeps

the inducer operating for 15-second postpurge.

— The circulator continues to operate.

8.

Lower

room thermostat setting to stop call for heat. Ther-

mostat is satisfied — Pilot and main gas valves are closed

— Inducer operates for 15-second postpurge — Circulator

is shut off.

9. Boiler is now in the

off cycle

.

10.

Repeat

steps

1

through

6

several times to verify operation.

11.

Return

the thermostat to normal setting.

12. Set thermostat heat anticipator setting to 0.4 amps, adjusted

for gas valve and control current.