CGs-4E Gas-Fired Water Boiler — Boiler Manual

Service & maint. — annual start-up

10b

Review with owner

1. Review the

User’s Information Manual

with the

owner.

2. Emphasize the need to perform the maintenance

schedule specified in the

User’s Information

Manual

(and in this manual as well).

3. Remind the owner of the need to call in a licensed

contractor should the boiler or system exhibit any

unusual behavior.

4. Remind the owner to follow the proper shutdown

procedure and to schedule an annual start-up at the
beginning of the next heating season.

Cleaning boiler

heating surfaces

The boiler contains ceramic fiber

and fiberglass materials. Use care

when handling these materials per

instructions on

page 64

of this

manual. Failure to comply could

result in severe personal injury.

1. Shut down boiler:

• Follow “

To Turn Off Gas to Appliance

instructions on boiler and

Operating instruc-

tions

.

• Do not drain boiler unless it will be exposed

to freezing temperatures. If using antifreeze in

system, do not drain.

2. Follow shutdown procedure.

3. Remove venting system connection to boiler.

4. Remove top jacket panel. Turn back insulation.

5. Remove collector box/transition assembly. Clean

sealant from assembly and sections.

6. Remove radiation plates hanging between sec-

tions.

7. Remove burners from base. Brush and vacuum

burners to remove all dust and lint. Verify that all

burner ports are free of debris.

8. Place newspapers in base of boiler to collect soot.

9. Clean between sections with wire flue brush.

10. Remove newspaper and soot. Vacuum or brush base

and surrounding area.

11. Reinstall radiation plates.

12. Replace collector box/transition assembly. Seal with

sealant. Obtain gas-tight seal to prevent flue gas

spillage and carbon monoxide emissions, resulting

in severe personal injury or death.

13. Replace insulation and jacket top panel.

14. Start up boiler following Section

7

of this manual

and the boiler

Operating instructions

(Section

9c

of this manual). Excessive sooting indicates im-

proper gas combustion. If found, check for proper

combustion and make any necessary adjustments.