Prepare boiler location — codes & checklist, Cgs-4e gas-fired water boiler — boiler manual, Installations must follow these codes – Weil-McLain GOLD CGS-4E User Manual

Page 6: Before locating the boiler, check the following

Advertising
background image

Part number 550-110-282/1108

6

GOLD

CGs-4E Gas-Fired Water Boiler — Boiler Manual

Prepare boiler location — codes & checklist

1a

Installations must follow these codes:

• Local, state, provincial, and national codes, laws, regulations and ordinances.
• National Fuel Gas Code, ANSI Z223.1–latest edition.
• Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/

ASME CSD-1, when required.

• National Electrical Code.
• For Canada only: B149.1 or B149.2 Installation Code, CSA C22.1 Canadian Electri-

cal Code Part 1 and any local codes.

The CGs-4E boiler gas manifold and controls met safe lighting and

other performance criteria when boiler underwent tests specified
in ANSI Z21.13–latest edition.

Before locating the boiler,
check the following:

• Check for nearby connection to:

• System water piping
• Venting connections
• Gas supply piping
• Electrical power

• Check area around boiler.

Remove any combustible materials, gasoline and

other flammable liquids, or other contaminants

.

Failure to keep boiler area clear and free of

combustible materials,

gasoline and other flammable liquids and vapors

can result in

severe personal injury, death or substantial property damage.

• Boiler must be installed so that gas control system components are protected from

dripping or spraying water or rain during operation or service.

• If new boiler will replace existing boiler, check for and correct system problems,

such as:
1. System leaks causing oxygen corrosion or section cracks from hard water

deposits.

2. Incorrectly-sized expansion tank.
3. Lack of antifreeze in boiler water causing system and boiler to freeze and

leak.