4. Hardware Installation

4.1. Connecting Power to the APS Unit

The APS-8/16M is available in both AC and DC powered versions. When

connecting power, proceed as follows:

CAUTION:

• Before attempting to install this unit, please review the warnings

and cautions listed at the front of the user's guide.

• This device should only be operated with the type of power

source indicated on the instrument nameplate. If you are not

sure of the type of power service available, please contact your

local power company.

4.1.1.

AC Powered Units

Plug the power cable (supplied with the unit) into the receptacle on the back

panel, and then connect the power cable to an appropriate, grounded outlet.

The APS features a self adjusting power supply that automatically adapts to

power supplies between 100 and 240 VAC. Press the Power Switch ON. The

ON LED should light and the RDY LED should begin to fl ash.

4.1.2.

DC Powered Units

The DC terminal block features two bus inputs as shown in Figure 4.1. This

allows the user to connect only one DC power source, or connect two DC

power sources where the second source serves as a backup. When connecting

the APS-8/16M to your DC power source, fi rst remove the protective cover

from the terminal block, attach the wires from the -48V DC power source to

the screw terminals, connect your ground line to the labeled ground screw, and

then replace the protective cover.

Figure 4.1: Terminal Block Assembly (DC Units Only)