Warnings and Cautions:

INSTALLATION INSTRUCTIONS

Secure Racking
If Secure Racked units are installed in a closed or multi-unit rack assembly,

they may require further evaluation by Certification Agencies. The following

items must be considered.
1. The ambient within the rack may be greater than room ambient.

Installation should be such that the amount of air flow required for

safe operation is not compromised. The maximum temperature for the

equipment in this environment is 45°C. Consideration should be given to

the maximum rated ambient.

2. Installation should be such that a hazardous stability condition is not

achieved due to uneven loading.

Input Supply
1. Check nameplate ratings to assure there is no overloading of supply

circuits that could have an effect on overcurrent protection and supply

wiring.

2. When installing 48 VDC rated equipment, it must be installed only per

the following conditions:
A. Connect the equipment to a 48 VDC supply source that is electrically

isolated from the alternating current source. The 48 VDC source is

to be connected to a 48 VDC SELV source.

B. Input wiring to terminal block must be routed and secured in such

a manner that it is protected from damage and stress. Do not route

wiring past sharp edges or moving parts.

C. A readily accessible disconnect device, with a 3 mm minimum

contact gap, shall be incorporated in the fixed wiring.

Grounding
Reliable earthing of this equipment must be maintained. Particular attention

should be given to supply connections when connecting to power strips, rather

than direct connections to the branch circuit.