WhisperKool XLT SERIES XLT 6000 User Manual

Page 8

Advertising
background image

Page 6

XLT 020111

Front of
WhisperKOOL

Wine Cellar

Exhaust Room

Intake

Exhaust

Unobstructed Airflow

Unobstructed airflow to and from the unit is a

critical factor in the unit’s overall performance.

Make sure there is a three-foot clearance in the

front of the unit, as fans blow down at an angle

and should not be obstructed by racking. There

should be a minimum three-foot horizontal clear-

ance from the rear of the unit as well. This will

assure that the unit can move the air around in

an efficient manner. Avoid the attempt to camou-

flage the unit by installing racking in front of the

unit. This will restrict airflow and thus the unit’s

ability to work efficiently.

Mounting the Unit

The unit should be mounted within 18 inches

of the top of the room in order to achieve suf-

ficient cooling. As the room cools down, the

warm air will rise to the ceiling. Mounting the

WhisperKOOL high in the room will create a

consistently cool environment by capturing the

warm air and replacing it with cool air. Mount-

ing the unit low in the room will result in a tem-

perature variation in the room due to the unit’s

inability to draw warm air from the ceiling of

the cellar to the unit itself.

Door

An exterior grade (1 3/4”) door must be installed as a cellar door. It is very important that weather strip-

ping is attached to all 4 sides of the door jam. A bottom “sweep” or threshold is also required. The door

must have a very good seal to keep the cool cellar air from escaping out of the cellar. One of the most

common problems with cooling units running continually is due to the door not sealing properly. In

cases where glass doors are used and the room size is close to the recommended unit size, the

next larger size WhisperKOOL should be used. This will compensate for the insulation loss due to the

lower insulating rating of glass.