Introduction

1–6

152315 Rev C

Environmental Specifications

The following environmental specifications are the same for both models of the
PV100S 100 kW Grid-Tied Photovoltaic Inverter.

Table 1-3 Environmental Specifications

Specification

Value

Dimensions

Inverter and DC Interface

Transformer and AC Interface

Overall System Footprint:

Layout Option A

Layout Option B

82 in H x 60 1/4 in W x 22 in D
(208 cm H x 153 cm W x 56 cm)

44 in H x 50 in W x 34 in D
(112 cm H x 127 cm W x 86 cm D)

12 ft W x 6 ft L (approximate)
(3.6 m x 1.8 m)
9 ft W x 7 ft L (approximate)
(2.7 m W x 2.1 m L)

Weight

Inverter and DC Interface
Transformer and AC Interface
Overall Weight

1000 lbs (approximate)
1400 lbs (approximate)
2400 lbs (approximate)

Allowable Ambient Temperature

Operating
Storage

-20 °C to 50 °C Maximum
-40 °C to 50 °C Maximum

Relative Humidity

To 95%, Non-condensing

Elevation

Power Derated above 6600 ft

Clearance (ventilation and
serviceability)

In front of access doors: 36 in (91 cm)
In front of access panels: 36 in (91 cm)
Sides: 12 in (30 cm)
Back: 6 in (15 cm)

Maximum Distance between Main
Inverter Enclosure and AC
Interface/Transformer Enclosure

15 ft (4.5 m)