Installation

3–16

152315 Rev C

5. Connect the AC power conductors in the Main Inverter Enclosure at TB4-A

(A phase), TB4-B (B phase), and TB4-C (C phase) with a box connector
using a 5/16" Hex screw. This hardware should be tightened to a torque value
of 275 in-lb (31 Nm). Connect the ground conductor to the TB1 terminal on
the ground bar on the left side of the enclosure. Torque this connection to
420 in-lbs (47.5 Nm).

Figure 3-15 AC Terminal Connections in the Main Inverter Enclosure

Figure 3-16 AC Terminal Connections in the AC Interface Enclosure

TB4-A

TB4-B

TB4-C

TB1 Ground Bar

AC Interface Enclosure

Enlargement of
Terminal Connectors
in the AC Interface
Enclosure

S1-4T2

(B phase)

S1-2T1

(A phase)

S1-6T3

(C phase)