Wiring - Specific

152315 Rev C

3–19

PV Array Connections

To make the connections from the PV Array/combiner to DC Interface
enclosure:
1. Remove the door clamps and open the door to the DC Interface Enclosure.
2. Route the PV Array cables conductors POSitive (PV+), NEGative (PV-), and

PV GND through the conduit to the DC Interface Enclosure, entering on the
underside.

3. The DC power conductor terminations are made at the TB3-1 (POS/DC+),

and TB3-2 (NEG/DC-) and TB3-3 (PV Gnd) locations. See Figure 3-19.

4. Terminations for the POSitive, NEGative, and GND conductors within the

DC Interface enclosure at the TB3 locations are made with box connector
using a 7/16" Hex Allen screw. The hardware should be tightened to a torque
value of 500 in-lbs. (56.5 Nm) for both the PV100S-480 and PV100S-208
systems.

5. Close the door to the DC Interface Enclosure and replace the door clamps.

Figure 3-19 PV Array Cable Routing and Terminations

PV POSitive Cable (TB3-1)

PV NEGative Cable (TB3-2)

Conduit entry from PV Array

GrouND (TB3-3)