Operator interface controls, Main enclosure door interlock switch – Xantrex Technology PV100S-480 User Manual

Page 27

Advertising
background image

Operator Interface Controls

152315 Rev C

1–7

Operator Interface Controls

Operator interface controls are located on the front door of the main inverter
enclosure. These controls include an ON/OFF Switch, 4-line LCD display and
keypad called the Universal Frontpanel Control Unit (UFCU). Additionally there
is an AC and DC Disconnect on the AC Interface Enclosure and the DC Interface
Enclosure Doors.

Main Enclosure Door Interlock Switch

The front door of the PV100S

main enclosure is equipped with an interlock switch

to preclude operation while the front door is open. Opening the door of the main
inverter enclosure will initiate an immediate controlled shutdown of the PV100S
and opens both the main AC and DC contactors. The main AC and DC contactors
cannot be closed unless the door’s interlock is in the engaged position. The
PV100S is prevented from being restarted until the door is again closed and the
switch is in the engaged position.
It is required that the PV100S

main enclosure door must be locked during normal

operation. The door interlock switch does NOT remove all hazardous voltages
from inside the inverter. Before attempting to service the PV100S, follow the
de-energize Lockout and Tag procedure on

page x

.

Figure 1-2 PV100S Operator Interface Components

DC Disconnect

Switch

LCD

Display

Universal
Frontpanel
Control
(UFCP)

ON/OFF

Switch

AC Disconnect

Switch

AC Interface Enclosure

(AC Side View)

Main Inverter Enclosure

(Front View)

Communication

Enclosure

DC Interface

Enclosure