Layout Options

The PV100S is shipped as two separate assemblies and can be arranged as shown
in Figure 2-1 or Figure 2-2.
The PV100S can be arranged in a number of different system layout options to fit
specific site requirements. The AC interface/transformer assembly may be
co-located adjacent to the left side of (or behind) the Main Inverter Enclosure up
to, and not exceeding, 15 feet away.
Given the flexibility to co-locate the AC interface/transformer assembly to fit a
desired system layout, the interconnect AC power conductors and conduit
between the Main Inverter Enclosure and the AC interface/transformer assembly
are to be supplied by the installer. See Figure 2-1 and Figure 2-2, depicting two
options for locating the AC interface/transformer assembly adjacent to the main
inverter.

Figure 2-1 PV100S Layout Option A

Transformer

Enclosure

Inverter

Enclosure

DC Interface

Enclosure

AC

Interface

Enclosure

Communications
Enclosure

6" Minimum Clearance

Minimum

Clearance*

(15' Max. Distance

from Inverter)

12"

Conduit

36"

Minimum

Clearance

36"

Minimum

Clearance

12' (3.6 m)

6'

(1.8 m)

36"

Minimum

Clearance

BASE: Concrete Floor or Pad

Approximately 12 ft by 6 ft

(3.6 m x 1.8 m)

Minimum

Clearance

12"

Minimum

Clearance

12"

36"

Minimum

Clearance

Minimum Dimension of Base:
Approximately 12 ft. by 6 ft. (3.6 m x 1.8 m)