Xantrex Technology PV100S-480 User Manual

Page 66

Advertising
background image

Installation

3–18

152315 Rev C

4. Connect the neutral conductor at TB6. Connect the ground conductor at TB2.

Terminations for the neutral and ground conductors within the AC Interface
Enclosure at the

TB6 and TB2 locations are made with 3/8-16" hardware.

Cables to these terminals must use a crimp-on type ring terminal or
compression-type lug and should be tightened to a torque value of 228 in-lbs
(25.7 Nm) for TB6, and 420 in-lbs (47.5 Nm) for TB2 for both the
PV100S-480 and PV100S-208 systems. See Figure 3-18 for the location of
these terminals.

5. Close the door to the AC Interface Enclosure and replace the door clamps.

Figure 3-18 AC Terminal Connections from the Utility

S1-2T1

(A Phase terminal)

S1-6T3

(C Phase terminal)

S1-4T2

(B Phase terminal)

TB6 Neutral

Ground TB2

Conduit entry

from utility

Note: PV100S-208 shown in this photo.