Model ycas0440ec – York MILLENNIUM 28971AR User Manual
Page 35
YORK INTERNATIONAL
FORM 201.18-EG1
35
LCWT
AIR TEMPERATURE – CONDENSER (°C)
(°C)
25
30
35
40
45
50
kWo
kW
E
COP
kWo
kW
E
COP
kWo
kW
E
COP
kWo
kW
E
COP
kWo
kW
E
COP kWo
kW
E
COP
MODEL YCAS0440EC
5.0 1509.5 360.3 3.8 1454.9 413.0 3.3 1411.4 473.9
2.8 1375.9 543.0
2.4
1306.7 593.4
2.1 1017.9 516.8 1.9
6.0 1553.6 363.9 3.9 1496.7 417.0 3.3 1450.9 478.5
2.8 1413.8 548.6
2.4
1334.7 594.7
2.1 1023.9 510.3 1.9
7.0 1598.6 367.3 4.0 1539.3 420.9 3.4 1491.7 483.2
2.9 1452.6 554.2
2.5
1358.8 593.4
2.2 1031.7 504.5 1.9
8.0 1644.5 370.7 4.1 1582.7 424.7 3.5 1532.6 487.7
3.0 1492.2 559.8
2.5
1380.3 590.3
2.2 1039.2 498.7 2.0
9.0 1691.3 374.0 4.2 1627.3 428.6 3.5 1574.8 492.3
3.0 1532.3 565.4
2.6
1398.2 585.5
2.3 1045.9 492.6 2.0
10.0 1738.9 377.3 4.2 1672.2 432.4 3.6 1617.8 496.9
3.1 1569.0 568.4
2.6
1418.2 581.5
2.3 1053.8 486.9 2.0
11.0 1787.3 380.6 4.3 1718.2 436.2 3.7 1661.7 501.6
3.1 1605.3 570.7
2.7
1438.3 577.4
2.4 1061.6 481.3 2.1
12.0 1836.6 383.9 4.4 1765.1 440.1 3.7 1706.3 506.3
3.2 1642.0 573.0
2.7
1458.7 573.4
2.4 1069.4 475.8 2.1
13.0 1886.7 387.1 4.5 1812.8 444.0 3.8 1751.7 511.1
3.2 1679.7 575.3
2.8
1479.3 569.5
2.5 1077.1 470.3 2.1
NOTES:
1. kW
= Compressor Input Power
2. EER
= Chiller EER (includes power from compressors, fans, and control panel’s 0.8 KW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings based on 2.4 GPM cooler water per ton
5. Rated in accordance with ARI Standard 550/590.