Continued) – York MILLENNIUM 28971AR User Manual

Page 89

Advertising
background image

YORK INTERNATIONAL

FORM 201.18-EG1

89

NOTES (for pages 78 - 89)

1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all

other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to
the system #1 MCA values in the YCAS Tables: -17, add 15 amps; -28, add 12 amps; -40, add 7 amps; -46, add 6 amps; -58, add 5 amps.

2. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the

circuit, per N.E.C. 440 - 12A1.

3. Minimum recommended fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs. Minimum fuse rating

= (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,

per N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

5. Minimum recommended circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit. Minimum circuit breaker

rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per

U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + ( # fans x each fan
motor FLA).

7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), or (3)

indicate the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must be
determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on
the National Electric Code and using copper conductors only. Field wiring must also comply with local codes.

8. A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control

circuit grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.

9. The field supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the

available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.

10. Two-Compressor machines with single-point power connection, and equipped with Star (Wye)-Delta Compressor motor start must also

include factory-provided individual system circuit breakers in each motor control center. All 3 & 4 Compressor machines equipped with
Star-Delta compressor motor start must also include factory-provided individual system circuit breakers in each motor control center.

11. Consult factory for Electrical Data on units equipped with “High Static Fan” option. High Static Fans are 3.8 kW each.

12. FLA for “Low Noise Fan” motors: 200V = 8.0A, 230V = 7.8A, 380V = 4.4A, 460V = 3.6A, 575V = 2.9A.

13. Group Rated breaker must be HACR type for cUL Machines.

Electrical Notes

(Continued)

CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMER)

NO. OF

CONTROL

MCA

MAX DUAL

NON-FUSED

COMPRESSORS

POWER

(MAX LOAD

ELEMENT

DISCONNECT

SUPPLY

CURRENT)

FUSE SIZE

SWITCH SIZE

2

115V-1Ø

20A

20A

30A

3 or 4

115V-1Ø

30A

30A

30A

(Non-CE 50/60Hz)

3 or 4

115V-1Ø

25A

30A

30A

(CE 50Hz)

CONTROL POWER SUPPLY (UNITS WITH STANDARD CONTROL CIRCUIT TRANSFORMER)

NO. OF

CONTROL

MCA

RECOMMENDED

NON-FUSED

COMPRESSORS

POWER

(MAX LOAD

DUAL ELEMENT

DISCONNECT

SUPPLY

CURRENT)

FUSE SIZE

SWITCH SIZE

2

200V - 60 HZ

12.5A

30A

230V - 60 HZ

10.9A

30A

380V - 60 HZ

6.6A

15A

460V - 60 HZ

5.4A

15A

575V - 60HZ

4.3A

15A

3 or 4

380V - 60 HZ

9.9A

30A

460V - 60 HZ

8.2A

15A

575V - 60 HZ

6.5A

15A

Advertising