Electrical data, Continued) – York MILLENNIUM 28971AR User Manual

Page 84

Advertising
background image

YORK INTERNATIONAL

84

Electrical Data

(Continued)

OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION WITH INDIVIDUAL SYSTEM

CIRCUIT BREAKERS – 3 & 4 COMPRESSOR UNITS (SEE FIG. 7)

(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block (standard) or Non-Fused Disconnect (option)

in ‘Option Panel’. Individual System Circuit Breakers in each Motor Control Center.)

See page 89 for Electrical Data footnotes.

FIELD SUPPLIED WIRING

CHILLER

FIELD PROVIDED POWER SUPPLY

FACTORY PROVIDED (LUGS) WIRE RANGE

7

MODEL

YCAS VOLTS

MCA

1

MIN NF

OVER-CURRENT PROTECTION

13

TERMINAL BLOCK

NF DISC. SWITCH

DISC SW

2, 9

MIN.

3, 5

MAX.

4, 6

(LUGS) WIRE RANGE

(LUGS) WIRE RANGE

380

561

600

600

700

(2) 2/0-500

(2) 250-500

0250EC

460

464

600

500

500

(2) 1/0-300

(2) 250-500

575

372

400

400

450

(2) # 2-4/0

(3) 2/0-250

380

651

800

800

800

(2) 2/0-500

(3) 2/0-400

0270EC

460

534

600

600

700

(2) 2/0-500

(2) 250-500

575

427

600

500

500

(2) 1/0-300

(2) 250-500

380

678

800

800

800

(3) 1/0-300

(3) 2/0-400

0300EC

460

559

600

600

700

(2) 2/0-500

(2) 250-500

575

445

600

500

500

(2) 1/0-500

(2) 250-500

380

745

800

800

800

(3) 1/0-300

(3) 2/0-400

0330EC

460

612

800

700

700

(2) 2/0-500

(3) 2/0-400

575

487

600

600

600

(2) 1/0-300

(2) 250-500

380

835

1000

1000

1000

(3) 2/0-500

(4) 4/0-500

0360EC

460

689

800

800

800

(3) 1/0-300

(3) 2/0-400

575

550

600

600

600

(2) 2/0-500

(2) 250-500

380

896

1000

1000

1000

(3) 2/0-500

(4) 4/0-500

0400EC

460

739

1000

800

800

(3) 2/0-500

(4) 4/0-500

575

589

800

700

700

(2) 2/0-500

(3) 2/0-400

380

991

1200

1200

1200

(3) 2/0-500

(4) 4/0-500

0440EC

460

812

1000

1000

1000

(3) 2/0-500

(4) 4/0-500

575

647

800

800

800

(2) 2/0-500

(3 )2/0-400