Electrical data, Continued) – York MILLENNIUM 28971AR User Manual

Page 86

Advertising
background image

YORK INTERNATIONAL

86

Electrical Data

(Continued)

OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION – 2 COMPRESSOR UNITS (SEE FIG. 3)

(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block or Non-Fused Disconnect in ‘Option Panel’.

No Internal Branch Circuit Protection (Breakers) per Motor Control Center

10

)

CHILLER

FIELD-SUPPLIED WIRING

MODEL

VOLTS

FIELD PROVIDED POWER SUPPLY

FACTORY PROVIDED (LUGS) WIRE RANGE

7

YCAS

MIN NF

OVER-CURRENT PROTECTION

13

STANDARD

OPTIONAL NF

MCA

1

DISC SW

2, 9

MIN.

3, 5

MAX.

4, 6

TERMINAL BLOCK

DISC. SWITCH

380

218

250

250

300

# 2 - 300

#N/A

0090EC

460

182

200

200

250

# 2 - 4/0

# 14 - 250

575

143

150

175

175

# 2 - 4/0

# 14 - 250

380

227

250

250

300

# 2 - 300

250 - 500

0100EC

460

189

200

225

250

# 2 - 4/0

# 14 - 250

575

150

200

175

200

# 2 - 4/0

# 14 - 250

380

269

400

300

350

1/0 - 500

250 - 500

0110EC

460

225

250

250

300

# 2 - 300

# 14 - 250

575

181

200

225

250

# 2 - 4/0

# 14 - 250

380

280

400

350

400

1/0 - 500

250 - 500

0120EC

460

235

250

300

300

# 2 - 300

250 - 500

575

189

200

225

250

# 2 - 4/0

# 14 - 250

0130EC

460

273

400

300

350

# 1 - 500

(2) 3/0-250

575

217

250

250

300

# 1 - 500

# 6 - 350

0140EC

460

293

400

350

400

(2) # 2 - 300

(2) 3/0-250

575

234

250

300

300

# 1 - 500

# 6 - 350

0150EC

460

307

400

350

400

(2) # 2 - 300

(2) 3/0-250

575

246

400

300

300

# 1 - 500

(2) 3/0-250

0160EC

460

320

400

400

400

(2) # 2 - 300

(2) 3/0-250

575

257

400

300

350

# 1 - 500

(2) 3/0-250

0170EC

460

335

400

400

450

(2) # 2 - 300

(2) 3/0-250

575

268

400

300

350

# 1 - 500

(2) 3/0-250

0180EC

460

347

400

400

450

(2) # 2 - 300

(2) 3/0-250

575

277

400

350

350

(2) # 2 - 300

(2) 3/0-250

0200EC

460

375

400

450

500

(2) # 1 - 500

(2) 3/0-250

575

299

400

350

400

(2) # 2 - 300

(2) 3/0-250

0210EC

460

393

600

450

500

(2) # 1 - 500

(2) 250-500

575

313

400

350

400

(2) # 2 - 300

(2) 3/0-250

0230EC

460

407

600

450

500

(2) # 1 - 500

(2) 250-500

575

324

400

400

450

(2) # 2 - 300

(2) 3/0-250

See page 89 for Electrical Data footnotes.

Advertising