Dimensions – ycas0090 – 0100ec (si), Dimensions – York MILLENNIUM 28971AR User Manual

Page 42

Advertising
background image

YORK INTERNATIONAL

42

Dimensions –

YCAS0090 – 0100EC (SI)

LD05210

NOTES:

1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,

reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high
pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control
panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be
higher than the unit.

229

89

43

2235

229

(7) 13 CONDUIT K.O.'S

CONTROL ENTRY

(8) 22 DIA. HOLES

CONTROL ENTRY

51

25

25 TYP.

51

C

C

(8) 38,51,64 CONDUIT K.O.'S

POWER ENTRY

25 TYP.

44

57

3 SPA. @ 127

127

432

83

178

127

432

B

B

438

2321

OPTIONS PANEL

VIEW C-C

VIEW B-B

VIEW A-A

MICRO-COMPUTER
CONTROL CENTER

CONNECTION)

UNIT TO COOLER

49 (EDGE OF

POWER: MULTIPLE POINT WITH TERMINAL BLOCKS