Dimensions – ycas0130 - 0180 (english), Dimensions – York MILLENNIUM 28971AR User Manual

Page 48

Advertising
background image

YORK INTERNATIONAL

48

DO NOT USE unless

2-compressor unit with

multiple point power

SYS. #1

COILS

SYS. #2

COILS

MICRO-COMPUTER
CONTROL CENTER

OPTIONS PANEL

B

B

C

C

P

CONTROL
TRANSFORMER
SERVICE SWITCH

91 3/8"

1 13/16" (EDGE OF
UNIT TO COOLER
CONNECTION)

ALTERNATIVE

POWER OPENING

(7" WIDE X 21" HIGH)

VIEW A-A

LD03742

Dimensions –

YCAS0130 - 0180 (English)

NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,

reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pres-
sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 6'; rear to wall - 6'; control
panel end to wall - 4'; top - no obstructions allowed; distance between adjacent units - 10'. No more than one adjacent wall may be higher
than the unit.

VIEW C-C

VIEW B-B

CONTROL ENTRY
(12) 1/2"
CONDUIT K.O.'S

9"

28"

2" TYP.

4 3/4"

2"

12"

RECOMMENDED

POWER

OPENING

(21" HIGH)

7 1/2"

CONTROL

OPENING

(9" HIGH)

7"

42"

31 1/2"

2"

LD03742a

MODELS

MODELS

DIMENSION

130 - 140

150 - 180

P

17-1/4"

18"

Q

83"

107"