Identifying multi-wire branch circuits, Warning: shock hazard – Xantrex Technology DR1524W User Manual

Page 112

Advertising
background image

Multi-wire Branch Circuit Wiring

C–4

975-0012-01-02 Rev A

Identifying Multi-wire Branch Circuits

Identifying
characteristic

Multi-wire branch circuits can be identified by removing the cover on the load
center and inspecting the wiring. Conventional 120 Vac circuits are identified by a
2-wire-plus-ground (black, white, and copper) “romex” for each circuit.
Multi-wire branch circuits use a 3-wire-plus-ground arrangement (black, red,
white and copper) for each circuit run.
If this arrangement exists in the panel and it is being powered by a stand-alone
120 Vac inverter, a potential fire hazard exists! For safety, these circuits must be
rewired to meet code.

WARNING: Shock Hazard

The next step involves opening the load center, exposing live circuits. This
procedure should only be performed by qualified persons or electricians.

Figure C-4 Multi-wire Branch Circuit Wiring

Ground Bare

Copper

Single Neutral

White

Red From L2

Breaker

Red From L1

Breaker

To Branch Circuits

Advertising
This manual is related to the following products: