Over discharge protection (odp) – Xantrex Technology DR1524W User Manual

Page 65

Advertising
background image

Front Panel Controls and Indicators

975-0012-01-02 Rev A

3–9

Over Discharge Protection (ODP)

When enabled, ODP shuts down the inverter at a specified voltage (low battery
cutoff) to protect the batteries from over discharge damage. The inverter circuitry
calculates the lowest (safe) DC voltage (leaving approximately 20% battery
capacity) based on the position the Battery Type Selector switch and the amount
of current drawn by the load. Under no-load conditions this level is typically
between 11.8 and 12.0 Vdc (for a 12-volt battery bank).

Important:

The range of set points between 2 and 5 o’clock also determine the low AC

Transfer Voltage. This must be considered when adjusting this potentiometer with ODP
enabled (see Table 3-3).

Important:

When ODP is disabled (set points between 9 and 1 o’clock), the inverter is

programmed to shut OFF when the batteries reach approximately 8.5 Vdc (1.4166 V/cell)
for 12-Vdc systems (17 Vdc for 24-volt systems).

Figure 3-5 ODP Enabled/Disabled Positions

Figure 3-6 Automatically Calculated Discharge Cutoff Voltage per Cell

ODP Disabled

Range

ODP Enabled

Range

1

0.1

0.01

0.001

Discharge Rate/Battery Capacity

1.55

1.5

1.65

1.6

1.75

1.7

1.85

1.8

1.95

1.9

2

C

e

ll V

o

ltage

12 Vdc

9.0

9.6

10.2

10.8

11.4

12.0

24 Vdc

18.0

19.2

20.4

21.6

22.8

24.0