Battery Information

B–6

975-0012-01-02 Rev A

Considerations

When calculating battery bank size, consider the following:

Motors typically require 3 to 6 times their running current when starting.
Check the manufacturer’s data sheets for their starting current requirements.
If you will be starting large motors from the inverter, increase the battery bank
size to allow for the higher start-up current.

Refrigerators and ice-makers typically run only about 1/3 of the time,
therefore, the running wattage is 1/3 of the total wattage of the appliance.
Divide the total wattage of the appliance by 3 when determining the battery
requirements.

Amp Hour Example Worksheet

Complete the following steps to calculate the amp-hour requirements per day for
your system. Use and Table B-2 as examples to complete your own.
To calculate amp-hour requirements:
1. Determine the loads the inverter will power and enter their wattage in the

watts column.

2. Determine the number of hours (or decimal portion of hours) the appliance is

used each day. Enter this figure in the Hours column.

3. Determine the number of days the appliance will be used during the week.

Enter this figure in the Days column.

4. Multiply Hours x Days for each load identified to determine the watt/hours

per week.

5. Add the total watt/hours per week for all loads then divide by 7 to obtain the

average total watt/hours per day.

6. Divide the total average per day by the DC nominal voltage.

This figure represents the average amp-hours per day that you will use.

Table B-1 Determining Average Daily Load in Amp-hours (Example

Load

Watts

Hours per Day

Days per
week used

Weekly
watt-hours

5 lights: 15 W CFL

75 W

5

7

2625

Breadmaker

1200

0.75

2

1800

Energy-efficient
refrigerator

200 x 0.3

24

10080

Laptop computer

50

6

5

1500

Total weekly watt-hours of AC load

16005 Wh

Divided by days per week

7

Average total watt-hours per day

2286

Divided by DC nominal voltage

24

Average amp-hours per day (Ah/d)

95