Mounting, Ventilation, Tools required – Xantrex Technology DR1524W User Manual

Page 27

Advertising
background image

Pre-installation Planning

975-0012-01-02 Rev A

2–3

Mounting

The National Building Code requires the inverter be mounted on a vertical surface
(or wall). The keyhole slots must not be used as the only method of mounting. The
purpose of the wall mounting requirement is to orient the inverter so that its
bottom cover, which has no holes, will not allow burning material to be ejected in
the event of an internal fire. Use 0.25-inch diameter bolts for mounting. The
mounting surface must be capable of supporting twice the weight of the inverter to
comply with UL 1741.

Ventilation

Install the inverter in a well ventilated area/enclosure for proper operation. The
inverter’s thermal shutdown point will be reached sooner than normal in a poorly
ventilated environment, resulting in reduced peak power output and surge
capability, as well as shorter inverter life.
The inverter contains an internal fan. Ensure the air vents and intakes are not
obstructed in any way. Provide a minimum clearance of 6 inches around the top
and sides of the inverter for ventilation.

Tools Required

The following tools may be required to complete this installation.

#2 Phillips screw driver

Slotted screw driver

Assorted open-end wrenches

Socket wrench and fittings

Multimeter (True rms)

Hole saw

Level

Wire strippers

Torque wrench

Electrical tape

Pencil

Utility knife