Measured inverter output is too low.

Alarm is sounding.

Possible Cause

Suggested Remedy

A standard “average-reading”

AC voltmeter has been used to

measure output voltage, resulting

in an apparent reading 5-15 volts

too low.

For accurate measurement, the

XPower modified sine wave output

requires a “true RMS” voltmeter for

accurate measurements.

The battery voltage is too low.

Recharge the battery.

Possible Cause

Suggested Remedy

Low voltage shutdown or

thermal shutdown has occurred.

Shorten cables or use heavier

cables. Recharge battery. Allow unit

to cool. Improve air circulation

around unit. Locate units in a cooler

environment. Reduce load if

continuous operation is required.