Battery run time is less than expected.

The AC load will not operate. The

FAULT

light is on.

Possible Cause

Suggested Remedy

The AC product power

consumption is higher than rated.

Use a larger battery to make up for

the increased power requirement.

The battery is old or defective.

Replace the battery.

The battery is not being charged

properly.

Some chargers are not able to fully

recharge a battery. Make sure that

you use a powerful charger.

Power dissipation in DC cables.

Use shorter/heavier DC cables.

Possible Cause

Suggested Remedy

The AC product(s) connected are

rated at more than the inverter’s

continuous power rating;

overload shutdown has occurred.

Use a product with a power rating

less than the inverter’s continuous

power rating (see

Table 1 on

page 30

).