Table 7: dnp048 cooling capacities - 4 ton, Dnp048 cooling capacities - 4 ton, All sensible capacity – York DNP036 User Manual

Page 13

Advertising
background image

036-21366-007-A-1205

Unitary Products Group

13

TABLE 7: DNP048 COOLING CAPACITIES - 4 TON

TEMPERATURE

OF AIR ON

CONDENSER COIL

AIR ON EVAPORATOR COIL

1,400 CFM

1,600 CFM

WB °F

WB °F

72

67

62

57

72

67

62

57

85 °F

NET CAP.

MBH

54.0

49.2

45.6

45.9

55.2

50.4

46.6

46.9

TOTAL POWER

INPUT kW

3.69

3.66

3.62

3.57

3.85

3.83

3.79

3.73

Se

nsible Cap

a

city

MBH

1

Ent

e

ring

Dry

Bu

lb

°

F

86

35.8

43.7

45.6

45.9

39.1

47.7

46.6

46.9

83

31.7

39.6

44.6

45.3

34.5

43

46.6

46.9

80

27.7

35.6

42.4

43.6

29.8

38.3

45.7

46.9

77

23.6

31.6

38.4

39.5

25.1

33.7

41

42.3

74

19.6

27.5

34.3

35.5

20.5

29

36.3

37.6

71

-

23.5

30.3

31.4

-

24.3

31.7

32.9

68

-

19.4

26.2

27.4

-

19.7

27

28.3

95 °F

NET CAP.

MBH

51.8

46.8

43.8

44.0

51.9

46.9

43.9

44.2

TOTAL POWER

INPUT kW

4.07

4.04

4.01

3.99

4.21

4.18

4.15

4.12

Sen

s

ib

le Cap

a

city

MBH

1

E

n

te

ring Dry

Bu

lb

°

F

86

35.4

42.9

43.8

44.0

38.4

46.4

43.9

44.2

83

31.4

38.9

42.8

43.2

33.8

41.7

43.9

44.2

80

27.4

34.9

40.9

41.5

29.1

37.1

43.5

44.2

77

23.3

30.8

36.8

37.5

24.4

32.4

38.8

39.5

74

19.3

26.8

32.8

33.4

19.8

27.7

34.1

34.8

71

-

22.7

28.7

29.4

-

23.1

29.5

30.2

68

-

18.7

24.7

25.4

-

18.4

24.8

25.5

105 °F

NET CAP.

MBH

48.7

44.3

41.4

41.7

49.2

44.7

41.8

42.1

TOTAL POWER

INPUT kW

4.49

4.45

4.38

4.34

4.63

4.59

4.51

4.48

Sensib

le C

a

p

a

city

MB

H

1

En

ter

ing Dry

Bul

b

°

F

86

34.1

41.3

41.4

41.7

37.1

4.44

41.8

42.1

83

30.0

37.7

40.7

41.1

32.4

40.6

41.8

42.1

80

26.0

33.6

38.9

39.4

27.8

35.9

41.6

42.1

77

22.0

29.6

34.9

35.3

23.1

31.3

36.9

37.4

74

17.8

25.6

30.8

31.3

18.4

26.6

32.3

32.7

71

-

21.5

26.8

27.3

-

21.9

27.6

28.1

68

-

17.5

22.8

23.2

-

17.3

22.9

23.4

115 °F

NET CAP.

MBH

45.7

41.8

39.1

39.4

46.4

42.5

39.7

40

TOTAL POWER

INPUT kW

4.91

4.86

4.74

4.70

5.05

5

4.87

4.83

S

ensible

Cap

a

c

ity

MBH

1

E

n

te

ri

ng

D

ry

Bulb

°

F

86

32.7

39.7

39.1

39.4

35.8

42.5

39.7

40

83

28.7

36.5

38.7

38.9

31.1

39.5

39.7

40

80

24.6

32.4

37.0

37.2

26.4

34.8

39.7

40

77

20.6

28.4

32.9

33.2

21.8

30.1

35

35.3

74

16.6

24.4

28.9

29.1

17.1

25.5

30.4

30.6

71

-

20.3

24.9

25.1

-

20.8

25.7

26

68

-

16.3

20.8

21.1

-

16.2

21

21.3

125 °F

NET CAP.

MBH

42.7

39.3

36.8

37.0

43.6

40.2

37.6

37.9

TOTAL POWER

INPUT kW

4.3

5.3

5.1

5.0

5.5

5.4

5.2

5.2

Se

nsible Cap

a

city

MBH

1

En

te

ri

n

g

D

ry

Bu

lb

°

F

86

31.4

38.0

36.8

37.0

34.5

40.5

37.6

37.9

83

27.3

35.3

36.7

36.8

29.8

38.4

37.6

37.9

80

23.3

31.2

35.1

35.1

25.1

33.7

37.6

37.9

77

19.2

27.2

31.0

31.0

20.5

29

33.2

33.2

74

15.2

23.1

27.0

27.0

15.8

24.4

28.5

28.5

71

-

19.1

22.9

23.0

-

19.7

23.8

23.9

68

-

15.1

18.9

18.9

-

15

19.2

19.2

1.

These capacities are net capacities (the indoor fan heat is deducted).