Field wiring diagram control wiring, 12 additional static pressure resistance, 2, 2-1/2, 3 ton – York DNP036 User Manual

Page 18: 13 additional static pressure resistance, 1/2, 4 and 5 ton, Programmable thermostat only, Thermostat unit terminal strip, 24 volt transformer

Advertising
background image

036-21366-007-A-1205

18

Unitary Products Group

FIGURE 3 - FIELD WIRING DIAGRAM CONTROL WIRING

TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON

DESCRIPTION

RESISTANCE, IWG

CFM

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

WET EVAPORATOR COIL

.01

.01

.01

.02

.03

.04

.05

.06

.07

.08

.09

.09

ECONOMIZER

1

.00

.00

.00

.01

.01

.01

.01

.02

.03

.04

.05

.06

FILTER FRAME KIT

.01

.02

.04

.06

.08

.10

.13

.16

.17

.18

.19

.20

1.

The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 13: ADDITIONAL STATIC PRESSURE RESISTANCE - 3-1/2, 4 AND 5 TON

DESCRIPTION

RESISTANCE, IWG

CFM

1,100

1,200

1,300

1,400

1,500

1,600

1,700

1,800

1,900

2,000

WET EVAPORATOR COIL

.02

.03

.04

.05

.06

.07

.07

.08

.09

.09

ECONOMIZER

1

.02

.02

.02

.03

.03

.04

.04

.04

.05

.05

FILTER FRAME KIT

.04

.04

.05

.05

.06

.07

.08

.09

.10

.11

1.

The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

R

G

W

R

G

C

Y

Y

W

C

PROGRAMMABLE

THERMOSTAT ONLY

**

** = Minimum wire size of 18 AWG

wire should be used for all
field installed 24 volt wire.

THERMOSTAT

UNIT TERMINAL STRIP

NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.

24 VOLT
TRANSFORMER