Table 15: unit dimensions front, Table 16: unit minimum clearances, Unit dimensions - front – York DNP036 User Manual

Page 20: 15 unit dimensions front, 16 unit minimum clearances, Figure 5 - unit dimensions - front

Advertising
background image

036-21366-007-A-1205

20

Unitary Products Group

FIGURE 5 - UNIT DIMENSIONS - FRONT

3 - 3 / 4

2 - 1 / 2

4 7 - 1 / 4

1 - 1 / 2

2 - 5 / 8

3 - 1 / 3

5 - 3 / 8

1 1

1 2 - 3 / 4

4 9 - 1 / 8

A

2 - 3 / 8

V E N T A I R O U T L E T H O O D

B L O W E R S E R V I C E

A C C E S S C O M P A R T M E N T

P A N E L

G A S S U P P L Y 1 - 1 / 4 " D I A .

H O L E ( 1 / 2 " N P T I

C O N N E C T I O N )

U N I T C O N D E N S A T E

C O N N E C T I O N 3 / 4 " N P T I

( T R A P R E C O M M E N D E D )

B

H I G H V O L T A G E

C O N N . 1 - 3 / 8 " D I A .

K N O C K O U T

H I G H V O L T A G E

C O N N . 7 / 8 " D I A .

K N O C K O U T

G A S S U P P L Y 1 - 1 / 4 " D I A .

K N O C K O U T ( 1 / 2 " N P T I

C O N N E C T I O N )

L O W V O L T A G E C O N N .

1 - 3 / 8 " D I A . K N O C K O U T

X 7 / 8 " H O L E

C O N D E N S E R C O I L

R E F R I G E R A N T

C O N N E C T I O N S

C O M B U S T I O N A I R

I N L E T L O U V E R S

F R O N T

G A S / E L E C T R I C C O N T R O L

S E R V I C E A C C E S S

C O M P A R T M E N T P A N E L

( O V E R A L L )

( O V E R A L L )

All dimensions are in inches.
They are subject to change with-
out notice. Certified dimensions
will be provided upon request.

TABLE 15: UNIT DIMENSIONS FRONT

UNIT SIZE

DIMENSION

“A”

“B”

024, 030, 036

33-1/2

18-1/4

042, 048, 060

41-1/2

23-1/8

TABLE 16: UNIT MINIMUM CLEARANCES

1

2

1.

A 1” clearance must be provided between any combus-
tible material and the supply air ductwork.

2.

The products of combustion must not be allowed to
accumulate within a confined space and recirculate.

CLEARANCES

FRONT

36”

BACK

0”

LEFT SIDE (Filter-Access)

24”

RIGHT SIDE

12”

BELOW UNIT

3

3.

Units may be installed on combustible floors made from
wood or class A, B, or C roof covering material.

0”

ABOVE UNIT

4

4.

Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.

36” (For Condenser Air Discharge)