TABLE 11: BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS

1

MODEL #

DNP

MODE

(COOLING / HEATING)

CFM

EXTERNAL STATIC PRESSURE - IWG

.20

.30

.40

.50

.60

.70

.80

.90

1.0

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

030

COOLING

(FACTORY SETTING)

1000

248

298

325

365

385

411

470

498

500

030

COOLING

(FIELD SETTING)

1250

342

385

431

474

510

562

614

657

694

030

HEATING (2 TUBE)

(FACTORY SETTING)

850

169

217

237

278

302

334

374

401

431

030

HEATING (3 TUBE)

(FACTORY SETTING)

1100

300

338

378

416

447

493

539

576

609

036

COOLING

(FACTORY SETTING)

1200

354

396

436

511

548

599

641

677

721

036

COOLING

(FIELD SETTING)

1350

442

503

563

606

648

685

721

774

826

036

HEATING (2 TUBE)

(FACTORY SETTING)

700

207

231

254

298

320

349

- - -

036

HEATING (3 TUBE)

(FACTORY SETTING)

1250

383

432

478

543

581

628

- - -

036

HEATING (4 TUBE)

(FACTORY SETTING)

1350

442

503

563

606

648

685

- - -

042

COOLING

(FACTORY SETTING)

1350

410

457

504

575

646

687

729

780

830

042

COOLING

(FIELD SETTING)

1500

450

500

553

641

729

798

830

872

939

042

HEATING (3 TUBE)

(FACTORY SETTING)

1500

450

500

553

641

729

798

830

872

939

042

HEATING (4 TUBE)

(FACTORY SETTING)

1275

388

433

478

545

612

652

691

739

787

048

COOLING

(FACTORY SETTING)

1400

427

476

525

599

673

716

759

812

865

048

COOLING

(FIELD SETTING)

1600

476

532

587

687

786

872

958

994

1030

048

HEATING (3 TUBE)

(FACTORY SETTING)

1525

458

511

564

654

744

814

- - -

048

HEATING (4 TUBE)

(FACTORY SETTING)

1600

476

532

587

687

786

872

- - -

048

HEATING (5 TUBE)

(FACTORY SETTING)

1600

476

532

587

687

786

872

- - -

060

COOLING

(FACTORY SETTING)

1500

345

487

554

569

654

745

784

835

896

060

COOLING

(FIELD SETTING)

1800

567

663

794

917

948

1015

1048

1155

1175

060

HEATING (3 TUBE)

(FACTORY SETTING)

1500

345

487

554

569

654

745

784

835

896

060

HEATING (4 TUBE)

(FACTORY SETTING)

1700

504

603

698

771

831

1043

1102

1155

1202

060

HEATING (5 TUBE)

(FACTORY SETTING)

1700

504

603

698

771

831

1043

1102

1155

1202

1.

Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 11