TABLE 8: DNP060 COOLING CAPACITIES - 5 TON

TEMPERATURE

OF AIR ON

CONDENSER COIL

AIR ON EVAPORATOR COIL

1,500 CFM

1,800 CFM

WB °F

WB °F

72

67

62

57

72

67

62

57

85 °F

NET CAP.

MBH

63.5

57.6

52.7

53.1

64.3

58.3

53.3

53.7

TOTAL POWER

INPUT kW

4.49

4.44

4.38

4.27

4.68

4.63

4.57

4.45

Se

nsible Cap

a

city

MBH

1

Ent

e

ring

Dry

Bu

lb

°

F

86

39.4

47.5

52.7

53.1

41.4

49.6

53.3

53.7

83

35.0

43.2

50.9

53.1

36.1

44.3

52.0

53.7

80

30.6

38.8

46.5

50.5

30.7

38.9

46.6

50.7

77

26.3

34.4

42.1

46.2

25.4

33.5

41.2

45.3

74

21.9

30.0

37.7

41.8

20.0

28.2

35.9

39.9

71

--

25.7

33.4

37.4

--

22.8

30.5

34.6

68

--

21.3

29.0

33.1

--

17.4

25.1

29.2

95 °F

NET CAP.

MBH

60.6

56.0

52.1

51.5

61.2

56.6

52.6

52.0

TOTAL POWER

INPUT kW

4.96

4.90

4.80

4.73

5.12

5.05

4.95

4.88

Sen

s

ib

le Cap

a

city

MBH

1

E

n

te

ring Dry

Bu

lb

°

F

86

38.2

46.6

52.1

51.5

43.3

52.6

52.6

52.0

83

33.9

42.2

49.8

51.5

38.0

47.2

52.6

52.0

80

29.5

37.8

45.4

48.7

32.6

41.9

50.3

52.0

77

25.1

33.5

41.1

44.4

27.3

36.5

44.9

46.7

74

20.7

29.1

36.7

40.0

21.9

31.1

39.5

41.3

71

--

24.7

32.3

35.6

--

25.8

34.2

35.9

68

--

20.3

27.9

31.2

--

20.4

28.8

30.6

105 °F

NET CAP.

MBH

57.6

53.3

49.5

49.3

58.4

54.1

50.2

50.0

TOTAL POWER

INPUT kW

5.52

5.43

5.34

5.27

5.69

5.60

5.51

5.43

Sensib

le C

a

p

a

city

MB

H

1

En

ter

ing Dry

Bul

b

°

F

86

37.1

45.3

49.5

49.3

42.6

51.8

50.2

50.0

83

32.7

40.9

48.4

49.3

37.2

46.4

50.2

50.0

80

28.4

36.6

44.1

46.4

31.8

41.1

49.1

50.0

77

24.0

32.2

39.8

42.1

26.5

35.7

43.7

44.7

74

19.6

27.8

35.4

37.7

21.1

30.3

38.3

39.3

71

--

23.4

31.0

33.3

--

25.0

33.0

33.9

68

--

19.1

26.6

29.0

--

19.6

27.6

28.6

115 °F

NET CAP.

MBH

54.6

50.6

46.9

47.1

55.7

51.6

47.9

48.0

TOTAL POWER

INPUT kW

6.07

5.97

5.89

5.81

6.26

6.16

6.07

5.99

S

ensible

Cap

a

c

ity

MBH

1

E

n

te

ri

ng

D

ry

Bulb

°

F

86

36.0

44.0

46.9

47.1

41.8

51.0

47.9

48.0

83

31.6

39.7

46.9

47.1

36.4

45.6

47.9

48.0

80

27.2

35.3

42.9

44.2

31.1

40.3

47.9

48.0

77

22.8

30.9

38.5

39.8

25.7

34.9

42.5

42.7

74

18.5

26.5

34.1

35.4

20.3

29.5

37.1

37.3

71

--

22.2

29.7

31.0

--

24.2

31.8

31.9

68

--

17.8

25.4

26.7

--

18.8

26.4

26.6

125 °F

NET CAP.

MBH

51.6

47.9

44.4

44.9

52.9

49.1

45.5

46.0

TOTAL POWER

INPUT kW

6.62

6.51

6.43

6.35

6.82

6.71

6.62

6.54

Se

nsible Cap

a

city

MBH

1

En

te

ri

n

g

D

ry

Bu

lb

°

F

86

34.8

42.8

44.4

44.9

41.0

50.2

45.5

46.0

83

30.5

38.4

45.5

44.9

35.6

44.8

45.5

46.0

80

26.1

34.0

41.6

41.9

30.3

39.5

46.7

46.0

77

21.7

29.6

37.2

37.5

24.9

34.1

41.3

40.7

74

17.3

25.3

32.8

33.1

19.6

28.7

35.9

35.3

71

--

20.9

28.4

28.7

--

23.4

30.6

29.9

68

--

16.5

24.1

24.4

--

18.0

25.2

24.6

1.

These capacities are net capacities (the indoor fan heat is deducted).