The XW Automatic Generator Start

975-0239-01-01

5–11

The wires on the wiring harness can be extended to meet installation requirements. When
extending the wire harness, ensure that the extension wires are the same color as the wires
on the harness.
To install the XW Automatic Generator Start using the wiring harness:
1. Connect each wire on the harness to its intended wire or contact on the generator,

thermostats, or external switches.

2. Plug the harness into the connector on the bottom panel of the XW

Automatic Generator Start.

Wire Identification

Each wire on the harness is identified by a number and a color. The wire numbers are
shown in Figure 5-9 and their colors and functions are described in Table 5-3.

Wire Size and
Length

Required wire sizes for the external connections to the wiring harness are:

When planning the routing for external connections, ensure that wire lengths are sufficient
to plug the wiring harness into the XW Automatic Generator Start once all the external
connections are complete.

Table 5-2 Required Wiring Size Based on Length of Cable

0–30 ft. (9 m)

Over 30 ft. (9 m)

18 AWG

16 AWG

Figure 5-9 XW Automatic Generator Start Wiring Harness

Table 5-3 Contact Numbers and Functions

Wire
Number

Function

Wiring Harness
Wire Color

1

Thermostat 1 input

Yellow

2

Thermostat 1 return

Gray

3

Thermostat 2 input

Orange

4

Thermostat 2 return

Gray

5

External shutdown input

White/Black

6

External shutdown return

Gray