Inverter/Charger Installation

2–24

975-0239-01-01

AUX-RPO: User Remote Power Off (RPO)

Connecting JU-2 (AUX-RPO) and JU-3 (AUX-COM) terminals together through an
external switch (normal open contact) will provide the system shut off function if the
switch is closed.
The external switch if pressed overrides the control provided from the front panel.
If the external switch is cleared (not pressed), the system can be enabled back from the
front panel.
Select an external switch with normal open contact; consult your local system designer or
qualified technician for specific installation instructions.

User Line Wiring

Use twisted pairs of #24 AWG to #12 AWG for connections. Carefully route the wires
away from high power load cables to minimize noise effects on signal integrity.

AUX Port Terminal Assignments

Table 2-11 User Connector Terminals and Functions

Pin

Reference

Name

Function

JU-1

AUX+12V

+12 V User Voltage
Supply

+12 Vdc Voltage source: 0.25 Adc maximum

JU-2

AUX-RPO

Remote Power Off

Remote Power Off Logic Level: Active Low.
Connecting this signal shuts down system
operation.

JU-3

AUX-COM

Common Ground
Reference

Return Common Ground Reference for 12V,
Remote Power Off signals.

JU-4

Not Operational

Not Operational

Not Operational

JU-5

Not Operational

Not Operational

Not Operational