Xantrex Technology XW POWER SYSTEM XW4024-120/240-60 User Manual

Page 104

Advertising
background image

XW System Accessories Installation

5–12

975-0239-01-01

Connecting the Generator

To connect the XW Automatic Generator Start to a generator, you must identify the start
wiring configuration of the generator you want to use. Generators must be auto-start
capable, and generators equipped with remote operation connections are ideal.
If the generator is equipped for remote operation, you must examine the wiring of the
remote cable and connector (or read your generator’s documentation, if available) and
identify the following wires:

Ground

Start

Stop

Generator run signal, also known as the Hour Meter or Switched B+ (battery positive)

Wiring
requirements

To wire the XW Automatic Generator Start to the generator, you need #16 or #18 AWG
wire connected between contacts 12 to 20 on the wiring harness. How many of these wires
you connect and in which combination depends on your generator type.

Generator types

The XW Automatic Generator Start has 13 preset generator configurations, or “Gen
Types” (see the XW Automatic Start Owner’s Guide for details on Generator Types). To
ensure that the XW Automatic Generator Start is compatible with your generator’s starting
circuitry, you must select your type of generator from the XW Automatic Generator Start
menu on the XW System Control Panel after completing the installation.

7

External manual on input

White/Green

8

External manual off input

White/Red

9

External ON/OFF LED Indicator output

White/Blue

10

Constant 12/24 V B+ (battery positive) for External ON/OFF/LED
Indicator

Red

11

External ON/OFF/LED Indicator return (connected internally to
wire number 13)

Black

12

Generator run signal (switched B+) sense input

Violet

13

Generator run signal (switched B+) sense return (generator battery
negative)

Black

14

Relay 1 (Generator run/stop) Normally open contact

Blue

15

Relay 1 (Generator run/stop) Normally closed contact

White/Violet

16

Relay 1 (Generator run/stop) Common contact

Gray

17

Relay 2 (Generator start) Normally open contact

White

18

Relay 2 (Generator start) Common contact

Gray

19

Relay 3 (Preheat/cooldown) Normally open contact

Brown

20

Relay 3 (Preheat/cooldown) Common contact

Gray

Table 5-3 Contact Numbers and Functions (Continued)

Wire
Number

Function

Wiring Harness
Wire Color

Advertising
This manual is related to the following products: