Inverter/Charger Installation

2–10

975-0239-01-01

Terminal covers

Color-coded snap-on DC terminal covers are provided to prevent accidental contact with
the terminals. Terminal covers are required for all installations, even if a XW Conduit Box
is used. It is also recommended that the shank of the ring terminals (cable lugs) be covered
with heat shrink or some other form of insulation.

Torque Values for the XW Series Inverter/Charger

Table 2-2 Recommended Battery Cable Size Versus Length

Inverter Model

Up to 5 Feet (1.5 m) (90°C wire)

Up to 10 Feet (3 m) (90°C wire)

XW4024

#4/0 AWG (120 mm

2

)

#4/0 AWG (120 mm

2

)

XW4548

#2/0 AWG (70 mm

2

)

#4/0 AWG (120 mm

2

)

XW6048

#4/0 AWG (120 mm

2

)

#4/0 AWG (120 mm

2

)

Important:

The NEC/CEC requires both overcurrent protection and a disconnect switch for

residential and commercial electrical systems. These items are not supplied as part of the inverter,
but are included in the XW Power Distribution Panel.

Table 2-3 Battery Cable (in conduit) to Maximum Breaker/Fuse Size

Cable Size
Required

Maximum Breaker/Fuse
Size

#2/0 (00) AWG

175 amps

#4/0 (0000) AWG

250 amps

Table 2-4 Torque Values for AC Wiring (AC Terminals and Ground Bar)

Wire Size

Torque Value

AWG

In-lb

N-m

14–10

35

4

8

40

4.5

6–4

45

5

Table 2-5 Torque Values for the Chassis Ground Lug

Wire Size

Torque Value

AWG

In-lbs

N-m

6-4

45

5.1

3-2

50

5.6

Table 2-6 Torque Values for the Inverter Battery Terminals

Torque Value

Ft-lbs

N-m

15

20.4