Pre-Installation

975-0239-01-01

2–3

Clearance Requirements

Provide a minimum clearance of 6 inches (15 cm)—12 inches is preferred—around the top
and 6 inches (15 cm) at the bottom of the inverter for ventilation. There must be at least
three feet of clearance in front of the inverter. Ensure that the vents are not obstructed with
foreign objects and that the minimum clearances are met.

Mounting

The XW Power System is designed to be mounted on a vertical surface. The supporting
surface must be strong enough to support a minimum of 500 pounds (227 kg). To facilitate
installation, a wall mounting plate (Xantrex p/n 210-0462-01-01) is provided for each XW
Inverter/Charger and XW Power Distribution Panel. The mounting plate and hardware on
the XW Inverter/Charger and XW Power Distribution Panel are designed to meet
standards for structural and seismic stability. When properly installed, the system also
meets Section 59 of UL 1741 for Static Loads.

Figure 2-1 Clearance Requirements