Wiring, Dc terminal connector locations, Wire size and over-current protection requirements – Xantrex Technology XW POWER SYSTEM XW4024-120/240-60 User Manual

Page 85: Warning: shock hazard

Advertising
background image

Wiring

975-0239-01-01

4–9

Wiring

DC Terminal Connector Locations

Terminal connectors for DC wiring are located inside the wiring compartment. The labels
above the DC wiring terminals and inside the wiring compartment identify all the
connection points. See Figure 4-7.

Wire Size and Over-current Protection Requirements

The wiring, over-current protection devices (fuses and circuit breakers), and installation
methods used must conform to all national and local electrical code requirements.
Wiring must be protected from physical damage with conduit or a strain relief clamp.
The BTS, auxiliary output, and network cables must pass through a different conduit than
the conduits used for PV wiring and battery cables. Pull the BTS cable through the conduit
first as the connector may not fit if other wires have been pulled first.

Current rating

The XW Solar Charge Controller is rated for 60 A maximum I

sc

. Since PV outputs can

vary due to the array size or sunlight striking it, the safe minimum wire size must be
chosen for maximum array short-circuit current. Consult PV array manufacturer
specifications.

Minimum wire
gauge

For installations where the PV array output is the maximum allowable 60 A I

sc

, the

minimum allowable wire gauge is #6 AWG (13.3 mm

2

) copper wire with a 90 °C (194 °F)

insulation rating. This wire gauge is determined by electrical code requirements regarding
conduit knockout sizes, wire bending radius, and space available within the XW Solar
Charge Controller wiring compartment.
No crimp-on terminals or lugs are required.

Over-current
protection

Over-current protection must be installed for the battery and PV circuits to protect the XW
Solar Charge Controller from short circuits at its input and output. The NEC requires all
circuits to be protected with a device rated for 125% of the rating of the circuit.

Important:

Installations must meet all local electrical codes. Installations of this equipment

should only be performed by a qualified electrician or a Certified Renewable Energy (RE) System
Installer.

WARNING: Shock Hazard

Disconnect battery and PV sources before wiring.

Figure 4-7 DC Connection Terminals

CONNECTIONS DIAGRAM

BTS

AUX

XANBUS XANBUS

BATTERY

-

-

-

+

+

+

BATTERY

TERMINAL TORQUE REQUIREMENTS

15lbf.in (1.7 Nm) FOR #14-10 AWG WIRE

18lbf.in (2.0 Nm) FOR #8 AWG WIRE

20lbf.in (2.2 Nm) FOR #6 AWG WIRE

PV

PV