Calculating cable sizes, Warning: fire hazard – Xantrex Technology 1000 User Manual

Page 25

Advertising
background image

Installation

3–6

975-0127-01-01

Calculating Cable Sizes

To operate safely and effectively, the XPower 1000 needs proper cables
and fuses. Because the XPower 1000 has low-voltage and high-current
input, it is essential that you use low-resistance wiring between the
battery and the inverter to deliver the maximum amount of usable energy
to your load.

For safe and efficient operation, you will need to calculate cable sizes for
your:

DC input cables from the battery to inverter (one way)

Chassis ground cable from the grounding point to the chassis ground
screw on the inverter’s DC panel.

See Figure 3-3 on page 3–12.

Calculating Size of DC Input Cables

Refer to Table 3-1 to plan the DC input cabling for your particular
application:

Keep all cables as short as possible, and ensure that each cable
between the inverter and the battery is no longer than 5 feet (1.5 m).

Do not use aluminum cable. It has about 1/3 more resistance than
copper cable of the same size, and it is difficult to make good, low-
resistance connections to aluminum wire.

Xantrex recommends that you use oil resistant cable.

WARNING: Fire hazard

Never use a cable longer than 5 feet (1.5 meters). A cable longer than 5
feet (1.5 meters) can potentially generate enough heat to start a fire or
result in poor inverter performance.

Advertising