15. troubleshooting

Note

The high limit safety cut-out can respond at temperatures

below –15 °C. The appliance may be subjected to these

temperatures during storage or transport.

f

f Display the fault code (see chapter "Settings / Displaying the

fault code").

f

f The plugs are described in chapter "Specification / Wiring

diagrams and connections".

fault

Code Cause

f

f remedy

The heat-up time is very long and the

heat-up symbol lights up.

The flanged immersion heater is scaled up.

Descale the flanged immersion heater.

The safety valve is dripping and the

heat-up symbol does not light up.

The valve seat is contaminated.

Clean the valve seat.

The display flashes.

E2

The temperature sensor is faulty.

Check whether plug X10 is properly inserted.

E4

Check the temperature sensor.

E128

Communication between the electronic assemblies for

control unit and operation is faulty.

Check whether plugs X2 are inserted properly in both

assemblies. Check the assemblies and the connecting

cable.

The water does not heat up.

The heat-up symbol does not appear.

The display flashes.

E8

The high limit safety cut-out has responded.

Check the appliance and eliminate the cause. Press the

reset button (see diagram).

The high limit safety cut-out has responded because the

thermostat is faulty.

Remedy the cause of the fault. Replace the high limit

safety cut-out.

The high limit safety cut-out has responded because the

temperature has dropped below -15 °C.

Press the reset button (see diagram).

The booster heater does not switch on.

Check the button.

The flanged immersion heater is faulty.

Replace the flanged immersion heater.

The water does not heat up.

The display flashes.

E6

The temperature sensor is faulty.

Check whether plug X10 is properly inserted.

Check the temperature sensor.

reset button, high limit safety cut-out

f

f Isolate the appliance from the power supply.

f

f Undo the screws and remove the bottom cap.

f

f Disconnect the connecting cable from the electronic assem-

bly for operation, position X2.

1

26

�0

2�

07

�0

28

7

1 High limit safety cut-out reset button