Flow Sensor Section

Figure 23: Pulse or Sine

For most Data Industrial sensors, the sensor type is “Pulse”, and the “K” and “Offset” values can be found in the respective Flow

Sensor Manual
“Sine” is used for zero-crossing flow sensors (some turbine meters, etc )
Several flow rate and flow total units of measure can be selected from the pull-down menu

Temperature Sensor Section

Figure 24: Sensor Attributes

First choose the Sensor Type (10K Ω Thermistor, 100 Ω RTD, or 1K RTD)
The Calc(ulation) Mode has three selections Initially, it is best to choose “Absolute ” In this mode the Energy Rate and Total will

be calculated as a positive value regardless of the direction of energy flow
In the T1>T2 Mode, energy will only be calculated if the T1 sensor is warmer than the T2 sensor If T1 is cooler than T2, the

energy rate will remain at 0 0 and the energy total will not increase
In the T1<T2 Mode, energy will only be calculated if the T1 sensor is cooler than the T2 sensor
The T1= and T2= are simply for reference to indicate the current temperature readings
This is useful in using the zeroing feature explained on page 19

Data Industrial® 340 BN/MB BTU Energy Transmitter

Page 18