Rs-485 network test – Badger Meter 340 BN/MB Btu Energy Transmitter User Manual

Page 24

Advertising
background image

RS-485 Network Test

Figure 31: RS-485 Test

The Configuration Software has an RS-485 test program
Although it uses Modbus settings, it is testing RS-485 communication
The test requires connection to a COM port using the Data Industrial A302-20 RS 485 to RS-232 convertor cable This cable can

also be helpful with other diagnostics programs and devices that use an RS-232 port to communicate
When testing the RS-485 network, it is sometimes helpful to connect to some other location instead of directly to the 340

BN/MB Btu Energy Transmitter When testing in this way the RS-485 end connector can be removed, and the wires can be

connected directly to the RS-485 pairs
The following table may be helpful to make connections

302 Cable w/RS-485 End

340 BN/MB

340 N2

Series 3000

Red

RS-485 +

N2 +

RS-485B

White

RS-485 –

N2 –

RS-485A

Black

REF

REF

RS-485 Gnd

When the RS-485 Test button is selected the following screens appear:

Figure 32: Test Screens

Data Industrial® 340 BN/MB BTU Energy Transmitter