Energy calculation, Filter coefficients, Pulse output – Badger Meter 340 BN/MB Btu Energy Transmitter User Manual

Page 19

Advertising
background image

The Zero Temp Diff is a very powerful feature in this product which allows any inaccuracies of drift in the temperature

sensors, or the 340 BN/MB Btu Energy Transmitter temperature measurements, to be cancelled out
This correction can be either manually typed in or if the temperature sensors are known to be at exactly the same

temperature, the Zero Temp Diff button can be used to automatically zero the difference between the two readings To

correct for any erroneous entries, simply manually type 0 0 in both fields
This feature must be used with caution. If used incorrectly, the temperature readings will be incorrect and the energy rates

and totals will also be in error

Energy Calculation

Figure 25: Rate and Total Units

Select the units of measure for energy rate and total from the pull-down menus

Filter Coefficients

Figure 26: Filter Coefficients

For most applications leave the default setting of 5 If the flow rate or energy rates are unstable for some reason (from a

disturbed flow profile, for example) this value can be increased as needed

Pulse Output

Figure 27: Flow or Energy

The pulse output can represent either flow or energy Units will be the same as selected in the previous sections
Pulse width and pulse resolution will be selected based on the requirements of the receiving device and system requirements

Installation & Operation Manual