Connecting the rs-485 buss – Badger Meter 340 BN/MB Btu Energy Transmitter User Manual

Page 12

Advertising
background image

+

-

Po

wer In

AC C /DC

AC L /DC

Output LED

Output

Pulse Out +

Pulse Out -

Pulse Input

NOTE:

maximum sinking current

is 100 mA @ 36 VDC

Device

(-) (+)

Figure 12: Sample Pulse Output Wiring Diagram

Connecting the RS-485 Buss

As shown in the Sample Pulse Output Wiring Diagram, the position of jumpers on each 340 BN/MB Btu Energy Transmitter

and wiring between each transmitter and the RS-485 network are different depending on where the transmitter is installed,

that is, its nodal position For all but the final transmitter in a string, the three jumpers NT, PU and PD should be in the open

position, and only the (+) and (–) network terminals should be connected to the RS-485 buss For the final 340 BN/MB Btu

Energy Transmitter in a Modbus network, the three jumpers NT, PU and PD should be in the closed position, and all three

network terminals, (+), (–) and REF, should be connected to the Modbus buss

NOTE:

N

The 340 BN/MB Btu Energy Transmitter default Modbus or BACnet polling address must be changed before it is

introduced into an existing network to avoid possible address conflicts Please refer to programming instructions in

the previous section

Figure 13: Sample Wiring Diagram to Modbus Network

NOTE 1: Biasing, circuitry and resistors for PU, PD and NT terminals are integral parts of the 340 BN/MB Btu Energy

Transmitter
NOTE 2: For the final 340 BN/MB Btu Energy Transmitter in a given RS-485 network string, NT, PU and PD jumpers should be

in the closed position Otherwise, NT, PU and PD should be in the open position
NOTE 3: For the final 340 BN/MB Btu Energy Transmitter in an RS-485 string, all three network terminals, (+), (-) and REF,

should be connected to the buss Otherwise, connect only terminals (+) and (-) to the buss

Data Industrial® 340 BN/MB BTU Energy Transmitter

Page 12

July 2012

Advertising