Series 2000 Downwind Heater

ALWAYS DISCONNECT

AND LOCK OUT POWER

BEFORE WORKING ON

OR AROUND HEATER

OPERATING PROCEDURE

The control panel display showing initial start up.

All safety and high limit switches are checked upon

power up. If a safety or limit is open, the control dis-

plays it. The control cannot operate with a safety switch

error, and the fan cannot turn on with an error condi-

Standard electrical safety practices and codes should

be used when working with a heater. Refer to the

National Electric Code Standard Handbook by

the National Fire Protection Association. A quali-

fied electrician should make all wiring installa-

tions.

Power Up

The controller locks up with the main display alter-

nating between a "FAN" and "ON" message. This

may be bypassed by depressing and holding the

"FAN BYPASS" switch (lower right switch). Nor-

mal operating procedure should be to power up the

controller with the fan off.

If multiple heaters are tied together, and the

master detects that the slave fan is on (the air

switch stuck?), the master will lock up display-

ing "SLA ERROR". This condition may be by-

passed with the "FAN BYPASS" switch.

tion. There is no way to bypass an error condition. It

must be fixed. (See errors on page 21)

The air switch is also checked on power up.

The air switch must indicate no airflow. This is

necessary to check the function of the air switch.

However, if the operator forgets and turns the fan

on before the controller has been powered up,