11. Safety Circuit Shut Down Messages

PNEG-1458 T-Series Tower Dryer

55

Input/Output Generated Errors

The following is a list of errors that are generated with the Input/Output board located in the upper
control box.

Air System Failure

A shut down has occurred due to a air system that was installed with an integral safety switch that was in
the unit. The air system safety connections are located in the upper control box on the terminal strip. This
can occur if this safety looses 12 VDC to terminal J1-10 on the Input/Output board. This input is jumpered
on the terminal strip when it leaves the factory and is usually installed in the field by a qualified electrician.

Aux Load Overload

The motor overload relay has tripped on the aux load motor circuit located in the upper control box.
This can occur if this safety looses 12 VDC to terminal J1-05 on the Input/Output board. Push the
Red button on the overload to reset this error. This is caused from the motor operating with to much of a
work load, which in turn uses more current (amperage). If the problem reoccurs then check the motor
to make sure it is not being overworked. You may need to call an electrician to measure the motors
full load amps (FLA).

Aux Unload Overload

The motor overload relay has tripped on the aux unload motor circuit located in the upper control box. This
can occur if this safety looses 12 VDC to terminal J1-04 on the Input/Output board. Push the Red button
on the overload to reset this error. This is caused from the motor operating with to much of a work load,
which in turn uses more current (amperage). If the problem reoccurs then check the motor to make sure
it is not being overworked. You may need to call an electrician to measure the motors full load amps (FLA).

Load Motor Overload

The motor overload has tripped on the load motor overload located in the upper control box. This can occur
if this safety looses 12 VDC to terminal J1-03 on the Input/Output board. Push the Red button on the
overload to reset this error. This is caused from the motor operating with to much of a work load, which in
turn uses more current (amperage). If the problem reoccurs then check the motor to make sure it is not
being overworked. You may need to call an electrician to measure the motors full load amps (FLA).

Meter Rolls Failed

If you have the meter roll speed adjustment turned too low (not turning), this will cause this error message.
It also could indicate that you have a defective meter roll sensor, the metering roll drive system has failed
to turn or broken chain or jammed metering roll is a possibility. This can occur if the input is not receiving
a 5 volt pulse on terminal J4-04 on the Input/Output board.

Out of Grain

The dryer has run low on grain and the out of grain timer has timed out, shutting the dryer down. The
unload auger will continue to run so it can clean out the remaining grain before shutting down.