OSRAM OPTOTRONIC OT EASY 60 II User Manual
Page 9
Advertising

9
OT EASY 60
IV 2009
Installation
OT EASY 60 output connections
OT EASY 60
output side
24 V (+)
CH1 (R-)
CH2 (G-)
CH3 (B-)
CH4 (W-)
GND (-)
16 mm
6 mm
16 mm
6 mm
3-wire cable
(without PE)
Connecting the outputs
Connection lines between the control unit and LED modules:
•
Two 3-wire lines (without PE) with the same external diameter
•
Max. length: 10 m
•
Recommended line diameter:
1.5 mm² (line length < 5 m) or 2.5 mm² (line length > 5 m)
Proceed as follows:
Step
Task
1
Strip the 3-wire lines, remove the insulation and connect to the screw
terminals.
2
If the GND wire is unused, insulate it on the side of the LED module.
3
Use cable clamps.
J
K
K
J
Cable clamp
K
3-wire line (2 x)