Bit 12:
Not used.

Bit 13, Selection of set-up:
Bit 13 = is used to choose the active set-up. The function is only possible when Multi set-ups is selected in par. 0-10 Active Set-up.

NB!
In par. 8-55 Set-up select a selection is made to define how Bit 13 gates with the corresponding function on the digital inputs.

Bit 14:
Not used.

Bit 15, Reverse:
Bit 15 = “0” causes no reversing.
Bit 15 = “1” causes reversing.

NB!
Depends on par. 8-54 Reversing select.

5.6.3 Status Word According to GE Drive Control Profile (STW)

Bit

Bit value = 0

Bit value = 1

00

Control not ready

Control ready

01

Unit not ready

Unit ready

02

Coasting

Enable

03

No error

Error, trip

04

No error

Error (no trip)

05

Reserved

-

06

Not trip locked

Trip locked

07

No warning

Warning

08

Speed

≠ reference

Speed = reference

09

Local operation

Bus control

10

Out of frequency limit

Frequency limit OK

11

Not running

Running

12

No resistor brake fault

Resistor brake fault

13

Voltage OK

Voltage exceeded

14

Torque OK

Torque exceeded

15

No thermal warning

Thermal warning

AF-60 LP™ Micro Drive Operating Instructions

DET-579A

39